BLUF — short answer
The safest remote access to refrigeration is the kind where the controller’s interface cannot be seen from the internet at all. The October–November 2026 attacks on European stores were not hacker wizardry — they hit controllers with a web panel exposed on a public IP, often past end-of-support. Clean up access: take devices off the internet (including 4G/5G links), give your contractor a VPN or brokered connection, change default passwords, patch firmware and replace end-of-life units. Password changes and Strict mode raise the bar, but they do not close unauthenticated vulnerabilities.
Key facts:
- Since 11 October 2026, European retailers have faced waves of attacks on refrigeration controllers. French authorities attributed the October wave (~700 stores, at least 15 fires) to Shahid Kaveh, a unit linked to the IRGC; the 1–2 November wave spanned 11 countries and remains unattributed — investigators have not confirmed any link between the waves (CERT-FR report CERTFR-2026-CTI-009; ENISA; SecurityWeek).
- CERT-FR’s alert CERTFR-2026-ALE-012 (12–16 October 2026) names the affected families: Danfoss AK-SM and AK-SC controllers, plus Copeland xweb and Dixell xweb supervisors — devices whose whole purpose is remote maintenance by contractors.
- How the October attackers got in has not been confirmed. Changing a defrost cycle is a normal administrative function — valid credentials are enough. It is unknown whether any published vulnerability was used or whether the attackers simply logged into an exposed interface (Orange Cyberdefense).
- A password change and Strict mode alone are not enough. On 20 November 2026 Danfoss published advisory DSA-2026-12-01 (CVE-2026-129713, CVSS 9.3): an unauthenticated buffer overflow in a CGI handler of the AK-SM 8xxA series up to and including version 5.4.0. Midnight Blue described six flaws in the AK-SM800A — five in handlers that require no login at all, and a sixth in the gateway that enforces Strict mode itself.
- Some of these devices will never be patched. Copeland ended software support for XWEB EVO on 16 March 2026 — the latest 5.8.8 firmware is also the last. For such devices, CERT-FR states plainly that a restart or factory reset does not fix the problem.
- Government bodies confirm the scale of exposure. CISA, the FBI, HHS, USDA and DoT published a joint fact sheet (TLP:CLEAR) with mitigations on 5 November 2026; ENISA and the European Commission issued a joint statement on 4 November 2026 urging immediate reduction of exposure.
- Once flaws are published, exploitation follows within hours. VulnCheck, which disclosed 14 vulnerabilities in XWEB EVO on 13 November 2026 (including a daily admin password derived from the device MAC and date), saw the first attacks 1 hour 40 minutes after the CVE record went live.
What happened — facts without speculation
On the night of 11–12 October 2026, hundreds of French stores lost their cold chain — attackers forced continuous heating/defrost cycles, in some places up to around 50 °C. France’s CTI report of 9 November attributed the attack to the Shahid Kaveh unit linked to the IRGC. On the night of 1–2 November, similar incidents appeared in at least 11 countries — with no claims of responsibility and no confirmed connection to the first wave. In the background, refrigeration vulnerabilities have been documented since August by Claroty (23 flaws in XWEB Pro, fixed in firmware 1.13; AK-SM 800A flaws fixed in 4.2 and 4.3.1; Trane Tracer SC+ from v6.3), and on 12–13 November VulnCheck described 14 more flaws in XWEB EVO alongside automated, opportunistic scanning — separate from both sabotage waves.
Decision table: area → what we know → what it means for your business → action
| Area | What we know (source) | What it means for your business | 30-day action | 90-day action |
|---|---|---|---|---|
| Internet exposure | CERT-FR and CISA: exposing a controller panel on a public IP is against good practice | If the interface is on a public address, someone has probably already found it in a scan | Inventory: find every controller on a public IP (including 4G/5G) and take it off the internet | Standing rule: new OT devices never get a public IP by definition |
| Contractor access | CERT-FR: access only via VPN/protected network; contractor IP filtering is a temporary measure | Your refrigeration maintenance contract must describe a secure channel, not an open port | Move the contractor onto a VPN or brokered gateway; IP allowlist as a transitional bridge | Segregate the OT network in a dedicated VLAN with brokered access |
| Passwords and accounts | CERT-FR and CISA: change default passwords, unique credentials, MFA where feasible | “Admin/admin” on a device that controls temperature is a no-flaw-needed way in | Change every default password; unique accounts for contractor and company | MFA or certificates for remote contractor access; periodic rotation |
| Firmware and EOL | Danfoss DSA-2026-12-01: fix for CVE-2026-129713 only in upcoming 5.5.x; Copeland: no XWEB EVO fixes after 16 March 2026 | Not everything can be patched — part of the estate must be replaced | Patch where the vendor still supports; register versions and EOL dates | Replacement plan for end-of-life units; “keep offline” decision for unpatchable ones |
| Strict mode | Danfoss recommends Strict mode and will remove the option to disable it; Midnight Blue: the Strict-mode gateway itself is vulnerable (fw ≤5.3.2) | Strict is an extra layer, not a substitute for isolation | Enable Strict mode where firmware supports it | Track vendor advisories; no illusions about closing the attack surface |
| Detection and response | CISA: logging, setpoint limits with alerting, offline backups | Without temperature deviation alarms, you learn about it from customers | Review setpoints and defrost schedules; alerts on deviations | Logs/config backups; tabletop exercise for “setpoints changed remotely” |
| After an incident | CERT-FR: for EOL devices a factory reset is insufficient; missing secure boot can preserve changes | Recovery requires verification, not just a restart | Procedure: disconnect, verify setpoints/accounts, restore via secure channel | Contractual provisions with contractor and insurer about the remote channel |
The operator’s perspective — Marcin Białczyk
In the IT/OT audits I run, refrigeration keeps showing the same pattern: a device bought with the installation, configured quickly by the service contractor, on a public address “because it was convenient to check temperatures”. Nobody in the company knows the panel exists — until someone else finds it first. [[ADD — example from your own practice: sector/type of site, no client names]]
Second observation: the boundary of responsibility. The refrigeration contractor and the company often assume “cybersecurity is IT’s problem”, while IT doesn’t know the controller even has a network interface. The October attacks showed that this organisational gap is a real vector — in the French blood service case, the attackers entered through an external refrigeration equipment provider.
Third: the decision to replace end-of-life hardware is a business decision, not a technical one. [[ADD — how you help clients argue replacement costs vs risk]]
Frequently asked questions
If I change the default password and enable Strict mode, am I safe? It is the best available step, but it does not close the topic. Danfoss’s 20 November 2026 advisory describes a vulnerability that requires no login at all, and Midnight Blue researchers showed a flaw in the gateway that enforces Strict mode. The foundation is taking the device off the public internet — repeated by CERT-FR, CISA and the vendor itself.
Our refrigeration contractor requires remote access — call-outs cost a fortune otherwise. What do we do? Remote access is absolutely fine — if it is designed, not default: a VPN or brokered gateway, a unique account for the contractor, an IP allowlist as a transitional solution (CERT-FR notes it is not permanent), and change logging. It is also worth checking insurance conditions before cutting the existing channel.
We have controllers past end-of-support. Is a factory reset enough after an incident? No. CERT-FR states plainly that for end-of-life devices a reset removes any changes but the device remains vulnerable and will be attacked again. Midnight Blue notes that the lack of secure boot can let changes survive even a reset. The only durable path: take it off the internet and plan a replacement.
Are these attacks connected to the XWEB EVO flaws published in November? Unknown — and it must not be assumed. VulnCheck, who described the 14 XWEB EVO flaws, notes that the exploitation they observed was automated opportunistic scanning after the CVE publication, separate from the store sabotage waves. How the October attackers got in remains unconfirmed.
Who is responsible for the controller’s security — the company or the refrigeration contractor? Formally and practically: the company whose processes and stock the cooling protects. The maintenance contract should describe the remote access method just as precisely as the temperature parameters — it is a supply-chain element in the sense of NIS2.
What next?
If you don’t know how many controllers in your sites sit on a public IP and who has access to them — that is the first thing to check. At CHORS we run an IT/OT exposure audit that maps such devices and shows how to design contractor remote access without opening the door to everyone else. Let’s start with a conversation — contact.
Boundaries and assumptions
CHORS.NET is not a 24/7 SOC and does not guarantee detection of every incident. We do not certify NIS2 or KSC compliance and do not issue legal opinions on our own — for legal interpretation we work with law firms. The recommendations above rely on publicly available statements from CERT-FR, CISA, ENISA and vendors as of the publication date; conditions of a specific deployment depend on the environment. This material is informational and technical; it is not legal advice.
Author: Marcin Białczyk, Founder & Cybersecurity Operator at CHORS.NET Last updated: 23 November 2026
Sources:
- CERT-FR, alert CERTFR-2026-ALE-012 (12–16 October 2026): https://cert.cyber.gouv.fr/alerte/CERTFR-2026-ALE-012/
- CERT-FR, CTI report CERTFR-2026-CTI-009 (9 November 2026), as reported: https://therecord.media/france-blames-iran-for-fridge-cyberattacks
- CISA/FBI/HHS/USDA/DoT, TLP:CLEAR fact sheet (5 November 2026): https://www.ic3.gov/CSA/2026/261105.pdf
- ENISA + European Commission, joint statement (4 November 2026): https://www.enisa.europa.eu/news/joint-statement-on-cyber-incidents-in-refrigeration-systems-across-the-eu
- SecurityWeek, second wave (3 November 2026): https://www.securityweek.com/over-100-european-stores-hit-as-supermarket-fridge-attacks-resume/
- Danfoss, advisory DSA-2026-12-01 / CVE-2026-129713 (20 November 2026): https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2026-12-01/
- RH-ISAC / Midnight Blue, AK-SM800A flaws (17 November 2026): https://rhisac.org/general-blog/unpatched-danfoss-ak-sm800a-flaws-expose-refrigeration-controllers-to-remote-takeover/
- VulnCheck, 14 XWEB EVO flaws (13 November 2026): https://www.vulncheck.com/blog/copeland-xweb-evo-unauthenticated-root
- Claroty Team82, XWEB Pro / AK-SM 800A / Tracer SC+ (9 August 2026): https://claroty.com/team82/research/chilling-discoveries-unpacking-vulnerabilities-in-copeland-xweb-pro-controllers
- Orange Cyberdefense (cyberiack), CERT-FR context and Danfoss position (13 October 2026): https://www.cyberiack.com/articles/frigos-pirates-le-cert-fr-publie-une-alerte-sur-les-automates-danfoss-ak-sm/